🛡️ CVE-2022-31205
🟠 CVSS 7.5 — High ✅ No Known Exploit CWE-312 NVD
7.5
CVSS Score
0 Low4 Medium7 High9 Critical10

Description

In Omron CS series, CJ series, and CP series PLCs through 2022-05-18, the password for access to the Web UI is stored in memory area D1449...D1452 and can be read out using the Omron FINS protocol without any further authentication.

Details

Severity HIGH
CVSS Score 7.5
CVSS Vector CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N
CWE CWE-312
Public Exploit ✅ No
Source NVD
Published 2022-07-26
Updated 2026-06-08
Modified 2024-11-21
Fix URL N/A

Affected Packages

Software From version Fixed in
cp1w-cif41-firmware
sysmac-cj2h-firmware 1.5
sysmac-cj2m-firmware 2.1
sysmac-cp1e-firmware 1.30
sysmac-cp1h-firmware 1.30
sysmac-cp1l-firmware 1.10
sysmac-cs1-firmware 4.1

References

Third Party Advisory, US Government Resource https://www.cisa.gov/uscert/ics/advisories/icsa-22-179-02
Third Party Advisory https://www.forescout.com/blog/
Third Party Advisory, US Government Resource https://www.cisa.gov/uscert/ics/advisories/icsa-22-179-02
Third Party Advisory https://www.forescout.com/blog/

Similar Threats

Patch Gap Protection

Running software with known vulnerabilities?

BotEraser can help reduce exposure by blocking IPs associated with exploit activity — even before a patch is available.

Start Free →

No credit card required  ·  Results in minutes

ⓘ Data Notice: The information presented above has been compiled from publicly available internet sources. Boteraser aggregates this data solely for informational purposes and does not independently classify, evaluate, or endorse any findings about the vulnerabilities listed. The accuracy and completeness of this information is the sole responsibility of the original publishers. Boteraser and its operators accept no liability for any decisions made based on this data.