Description
Tinycontrol devices such as tcPDU and LAN Controllers LK3.5, LK3.9 and LK4 have two separate authentication mechanisms - one solely for interface management and one for protecting all other server resources. When the latter is turned off (which is a default setting), an unauthenticated attacker on the local network can obtain usernames and encoded passwords for interface management portal by inspecting the HTTP response of the server when visiting the login page, which contains a JSON file with these details. Both normal and admin users credentials are exposed. This issue has been fixed in firmware versions: 1.36 (for tcPDU), 1.67 (for LK3.5 - hardware versions: 3.5, 3.6, 3.7 and 3.8), 1.75 (for LK3.9 - hardware version 3.9) and 1.38 (for LK4 - hardware version 4.0).
Details
Affected Packages
| Software | From version | Fixed in |
|---|---|---|
| unknown | — | — |
References
Similar Threats
- Unknown CVE-2022-0003
- Unknown CVE-2022-0303
- High CVE-2022-1206
- Unknown CVE-2022-0931
- Unknown CVE-2022-0094
Exploit Protection
Help block exploit attempts
BotEraser is designed to detect and help reduce malicious bot traffic that may target known vulnerabilities on your site.
Try BotEraser Free →No credit card required · Results in minutes
ⓘ Data Notice: The information presented above has been compiled from publicly available internet sources. Boteraser aggregates this data solely for informational purposes and does not independently classify, evaluate, or endorse any findings about the vulnerabilities listed. The accuracy and completeness of this information is the sole responsibility of the original publishers. Boteraser and its operators accept no liability for any decisions made based on this data.